Description
Application
Cassette fan coil unit is an efficient air conditioning equipment, which is widely used in central air conditioning system. It is composed of a blower and a coil, and the blower is used to flow air through the coil, so as to realize the refrigeration or heating of the air.
Working Principle
High-efficiency refrigeration: The clip fan coil unit adopts high-efficiency heat exchanger with copper tube and aluminum fins, which has good heat transfer performance and can quickly take away the heat in the room to achieve high-efficiency refrigeration effect.
Energy saving and environmental protection: The clamped fan coil unit adopts low energy consumption and low noise motor, which runs stably and can automatically adjust the air volume according to the indoor temperature, effectively reducing energy consumption and meeting the environmental protection requirements.
Product Details
Equipped with a drainage pump. The advanced 4-way cassette Fan coil is equipped with a condensed water drainage pump, which is flexible in design and can easily remove condensed water.
cj
The condenser and the round condenser increase the heat dissipation area, and the heat dissipation is more evenly combined with multiple water inlet and outlet heads, which can accelerate the heat exchange speed and improve the heat exchange efficiency.
Fan: ceiling cassette fan coil unit the three-dimensional spiral blades ensure the air volume and thinner shape, and the irregular blade pitch greatly reduces the running noise
The air inlet filter is fixed by snap, which is convenient to disassemble and clean the filter screen.
Motor, the motor is a general motor with stable performance. The installation position of the motor is increased in density and thickened in rubber to
reduce the noise and resonance generated by the motor during operation.
Technical Data
Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
Cooling Ca. (kw)
(Water in 7℃) ( Air inlet temperature: DB 27℃,WB19.5℃) |
H | 1.98 | 2.98 | 3.68 | 4.98 | 5.4 | 7.2 | 9.9 | 10.8 | 12.6 |
M | 1.63 | 2.27 | 2.81 | 3.75 | 4.32 | 5.53 | 7.51 | 8.08 | 9.68 | |
L | 1.04 | 1.51 | 1.89 | 2.51 | 2.85 | 5.53 | 5.00 | 5.55 | 6.45 | |
Heating Ca. (kw)
(Water in 60℃) ( Air inlet temperature: DB 20℃) |
H | 2.97 | 4.80 | 5.48 | 7.20 | 8.1 | 10.80 | 14.50 | 16.20 | 18.90 |
M | 2.45 | 3.67 | 4.19 | 5.42 | 6.33 | 8.17 | 11.00 | 12.35 | 14.52 | |
L | 1.57 | 2.44 | 2.82 | 3.60 | 4.52 | 5.47 | 7.33 | 8.48 | 9.68 | |
Air flow(m³/h) | H | 345 | 510 | 690 | 875 | 1035 | 1375 | 1705) | 2045 | 2380 |
M | 280 | 390 | 520 | 640 | 790 | 1030 | 1290 | 1500 | 1800 | |
L | 180 | 260 | 350 | 430 | 520 | 690 | 860 | 1030 | 1200 | |
Power Input(W) | 50 | 50 | 58 | 72 | 92 | 126 | 128 | 152 | 198 | |
Current (A) | 0.151 | 0.225 | 0.258 | 0.32 | 0.385 | 0.561 | 0.547 | 0.677 | 0.882 | |
Noise dB (A) | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 49 | 52 | |
Static pressure (Pa) | 12 | |||||||||
Power Supply | 220-240v/1ph/50Hz | |||||||||
Control way | Wired or remote controller | |||||||||
Water flow (m³/h) | 0.42 | 0.52 | 0.62 | 0.86 | 0.98 | 1.08 | 1.58 | 1.78 | 1.92 | |
Water pressure drop(kPa) | 14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 46 | |
Water pipe for in/out | ZG3/4” |