Description
Application
Cassette Ceiling Mounted air conditioner fan coils can bring 360-degree uniform air outlet without a crash, with water as the medium to exchange cold and hot, which fully saves energy and protects the environment. The unique adjustment switch with three gears can select different comfortableness for different people so that everyone can feel the charm of the air conditioner and enjoy the temperature.
Working principle
To cool or heat indoor air or outdoor mixed air through the surface cooler and then send it into the room so that the indoor air temperature can be lowered or raised to meet people’s comfort requirements. Cold (hot) medium water in the coil pipe is supplied centrally by the machine room.
Product details
Equipped with a drainage pump. The advanced 4-way cassette Fan coil is equipped with a condensed water drainage pump, which is flexible in design and can easily remove condensed water .
The condenser and the round condenser increase the heat dissipation area, and the heat dissipation is more evenly combined with multiple water inlet and outlet heads, which can accelerate the heat exchange speed and improve the heat exchange efficiency.
Fan: ceiling cassette fan coil unit the three-dimensional spiral blades ensure the air volume and thinner shape, and the irregular blade pitch greatly reduces the running noise
The air inlet filter is fixed by snap, which is convenient to disassemble and clean the filter screen.
Motor, the motor is a general motor with stable performance. The installation position of the motor is increased in density and thickened in rubber to
reduce the noise and resonance generated by the motor during operation
Technical Data
Technical Data of 2 Pipe Fan Coils Unit | ||||||||||
Model and performance | FP34 | FP51 | FP68 | FP85 | FP102 | FP136 | FP170 | FP204 | FP238 | |
Rated air flow m3/h |
high | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
Medium | 280 | 390 | 520 | 640 | 790 | 1030 | 1290 | 1500 | 1800 | |
low | 180 | 260 | 350 | 430 | 520 | 690 | 860 | 1030 | 1200 | |
Rated cooling capacity W |
high | 1980 | 2980 | 3680 | 4980 | 5580 | 7200 | 9900 | 10800 | 12600 |
Medium | 1631 | 2279 | 2814 | 3750 | 4322 | 5534 | 7512 | 8088 | 9681 | |
low | 1048 | 1519 | 1894 | 2519 | 2854 | 5534 | 5008 | 5554 | 6454 | |
Rated heating capacity W |
high | 2980 | 4800 | 5480 | 7200 | 8180 | 10800 | 14500 | 16200 | 18900 |
Medium | 2454 | 3671 | 4191 | 5421 | 6335 | 8179 | 11005 | 12353 | 14521 | |
low | 1578 | 2447 | 2821 | 3600 | 4481 | 5479 | 7335 | 8482 | 9681 | |
The input power | W | 34 | 50 | 58 | 72 | 92 | 126 | 128 | 152 | 198 |
The amount of water m3/h |
0.42 | 0.52 | 0.62 | 0.86 | 0.98 | 1.08 | 1.58 | 1.78 | 1.92 | |
Water press loss Kpa |
14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 46 | |
Motor number | 1 | |||||||||
power | 220V~240/50HZ |
Technical Data of 4 Pipe Cassette Fan Coils Unit | ||||||||||
Model and performance | FP34 | FP51 | FP68 | FP85 | FP102 | FP136 | FP170 | FP204 | FP238 | |
Rated air flow m3/h |
high | 360 | 520 | 650 | 840 | 1000 | 1320 | 1660 | 1950 | 2090 |
Medium | 290 | 420 | 510 | 670 | 800 | 1050 | 1330 | 1560 | 1670 | |
low | 220 | 310 | 390 | 500 | 600 | 790 | 1000 | 1170 | 1250 | |
Rated cooling capacity W |
high | 1980 | 2980 | 3680 | 4980 | 5580 | 7200 | 9900 | 10800 | 12600 |
Medium | 1631 | 2279 | 2814 | 3750 | 4322 | 5534 | 7512 | 8088 | 9681 | |
low | 1048 | 1519 | 1894 | 2519 | 2854 | 5534 | 5008 | 5554 | 6454 | |
Rated heating capacity W |
high | 1950 | 3000 | 3750 | 4850 | 5750 | 7400 | 9700 | 10900 | 11850 |
Medium | 1700 | 2550 | 3200 | 4100 | 4850 | 6250 | 8200 | 9250 | 10050 | |
low | 1350 | 2000 | 2500 | 3250 | 3850 | 4950 | 6500 | 7300 | 7950 | |
The input power | W | 34 | 50 | 58 | 72 | 92 | 126 | 128 | 152 | 198 |
The amount of water m3/h |
0.42 | 0.52 | 0.62 | 0.86 | 0.98 | 1.08 | 1.58 | 1.78 | 1.92 | |
Water press loss Kpa |
14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 46 | |
Motor number | 1 | |||||||||
power | 220V~240/50HZ |