Description
Application
A slim exposed fan coil unit is a type of HVAC (Heating, Ventilation, and Air Conditioning) equipment that is designed to provide efficient heating and cooling in buildings. Here are some key functions and features of a slim exposed fan coil unit
Working Principle
The primary function of a slim exposed fan coil unit is to provide both heating and cooling to the indoor space it serves. It accomplishes this by circulating either hot water or chilled water through a coil and using a fan to blow air over the coil, thus transferring the thermal energy to the air.
Product Details
Increased the heat exchange area: 38.5mm thickness coil and 42 copper tube , distribulted are duct, Increased coil utilization rate.
Motor we adopted is the DC motor with low noise *Add silencer foam insulation to the air duct inside the unit to reduce the air flow noise.
h
The concentric positioning of the motor holder can ensure that the motor, fan and tail positioning cushion are in the same straight line, when the motor is running. So that it running stablely with low noise.
Two drain pans in the units,then the units can be installed vertical or horizontal
Technical Data
WATER CHILLED FAN COIL UNIT DATA SHEET | |||
Product name | Ultra-thin exposed FCU | ||
Product type | 2-pipe | ||
Product models | FP-85/136 | ||
Application | It is generally used for home, replaced the traditional radiator. | ||
Product function | It can be used for heating or cooling | ||
Power supply | 190-250V 50/60Hz | ||
Product components | Condenser | Fin | 0.105mm thickness aluminum fins,distance between fins is 1.2mm |
Cooper tube | 0.26mm thickness,7mm diameter,42 copper tubes in 3 rows | ||
Drain pan | Material | Steel sheet with 6mm insulation | |
Panel | 0.8mm Hot zinc sheet metal with white spray | ||
Motor | Low noise five speed DC fan motor | ||
Label | Labels: model label, wiring diagram, precautions, fan rotation logo, etc. | ||
Fan | ABS material cross flow fan with low noise | ||
Production technology | Tube | Mechanical expansion, automatic welding | |
Drain pan | One-time molding | ||
Body Panel | Fully automatic molding in one molding, with longitudinal reinforcement at the bend,and with high gloss spray surface treatment | ||
Motor panel | Hydraulic abrasive ribs+longitudinal reinforcement at the bend | ||
Inspection standards | 1. No scratches or rust on the surface of the machine | ||
2. The internal cooler of the machine has no leakage under the pressure of 1.6Mpa (hold pressure for at least 5min) | |||
3. The unit starts under the condition of 90% of the rated voltage and runs stably for 10 minutes | |||
4.Under normal temperature and humidity conditions, use 500V insulation resistance meter to measure the insulation resistance between the live part and non-metal live part of the unit is not less than 2MΩ |
Drawing
All figures in mm | ||
Model | FP-85 | FP-136 |
A total length | 950 | 1220 |
B air outlet length | 550 | 820 |
C air inlet length | 760 | 1030 |
D space between lifting holes | 611 | 881 |